Check transformer ratios and power accounting

Unit 2 · 4WPH2 · Specification 7.17P, 7.18P, 7.19P, 7.20P

An ideal transformer has 200 primary turns supplied with 6.0 V alternating voltage. Secondary turns are varied. Voltage readings use a consistent measurement convention; the model assumes 100% efficiency.

Example data

These are low-voltage alternating-current readings. Keep primary voltage/frequency and core fixed. The table alone does not measure real efficiency.

Plot and check the data

1. Check transformer ratios and power accounting

An ideal transformer has 200 primary turns supplied with 6.0 V alternating voltage. Secondary turns are varied. Voltage readings use a consistent measurement convention; the model assumes 100% efficiency.

Plot secondary voltage against secondary turns. Draw a straight line of best fit. [5 marks]

Results Example data
Secondary turnsSecondary voltage / V
1003
2006
3009
40012
50015
1 · Axes, labels and scales

Put Secondary turns (the independent variable) on the x-axis and Secondary voltage / V on the y-axis. This grid is 5 big squares across and 10 up; each big square has 5 × 5 small squares.

x-axis
y-axis
x-axis labely-axis label

Set your scales, then tap the grid to plot each point.

Keyboard and screen-reader entry

Values are placed using the scale you set, so a wrong scale still gives a wrong graph – just like on paper.

Stuck on the scale?

Use the turns ratio first. Higher output voltage does not create extra power in an ideal transformer.

Interpret the evidence

Use numbers and units from the results. Graph feedback checks plotting conventions; interpretation is self-assessed against the criteria.

5 marks

Data Gym

Use the evidence, then compare your reasoning

Check the 300-turn reading using the turns ratio and classify the 100-turn and 400-turn cases. For 400 turns, an output current of 0.50 A is measured: calculate output power and ideal input current. Explain why step-up transmission can reduce heating and state an important real-transformer limitation.

(5)

Answer using the evidence, then reveal the guidance. Tick one mark for each criterion met; equivalent scientific explanations are acceptable.

Total for this question: 5 marks

Reference graph and worked reasoning
Secondary voltage against Secondary turns. Transformer: (100, 3), (200, 6), (300, 9), (400, 12), (500, 15). Values and units are also in the results table.010020030040050002468101214161820Secondary turnsSecondary voltage / V
Reference graph for this example. Compare axes, units, scales, points and the requested line; use the table for precise values.
  1. At 500 secondary turns, Vs/Vp=15/6=2.5=500/200.
  2. Do not assume output current also rises with voltage while power stays fixed. Input and output current need not be equal.